ProcXpert
Share Your purchase requirement, Our ProcXpert team will Connect you to right Supplier.
Inquiry NowSupply Installation Testing in Udaipur - Complete Tender Details
Find eligibility criteria, important deadlines, bidding requirements, and download official documents for "Supply Installation Testing " in Udaipur, India.
NTID 45870030
- Opening Date : Sat 1st August, 2026
- Closing Date : Fri 31st July, 2026
- ₹ 1150000.00
- NTID 45870030
Tender Description
Documents
Get Complete Tender Details Now - Download the Document!
Download Now – Only ₹200-
Document-1
721.3 kBOil_India_ExtraDoc...Oil_India_ExtraDocument-GCO0449P23.pdf
-
Document-2
721.3 kBOil_India_ExtraDoc...Oil_India_ExtraDocument-GCO0449P23.pdf
Costs
-
EMD
23000.00 -
Document Cost
500.00 -
Estimated Cost
1150000.00
BOQ Items Total Items : 8 | Total Qty : 6
| # | Item | Quantity | Units |
|---|---|---|---|
| 1 | SITC OF ESE TYPE 03 LIGHTING ARRESTORS | ||
| 2 | Plate Earthing as per IS:3043 with copper Earth plate of purity >95% of size 600mm x 600mm x 3.0mm by embodying 3 mtr. Below the ground level with 20 mm dia. G.I. B class watering Pipe ,including all accessories like nut, bolts, reducer, nipple, wire meshed funnel, Heavy duty weather proof poly-propylene earth inspection chamber as per requirement of IS/IEC 62305 and tested as per IEC 62561-5 with lockable Jam free lid suitable for safe working load 60 Kn of round / square size 250 mm, and Height 250 to 300 mm. and embodying the pipe complete with alternate layers salt and coke/ charcoal, testing of earth resistance for value of 5 ohms or less as required. | 1.00 | PER SET |
| 3 | Supply & Laying following size B class , G.I. Pipe confirming to IS : 1239 P 1 ( 2004 ) with accessories like bend, socket etc. for laying earth conductor/ strip / cable in ground/ surface/ recess as required. (Earth Excavation will be Paid Extra) 25 mm dia. | 1.00 | PER SQMTR |
| 4 | Lightning Surge Counter designed to record and display lightning strike events. The counter shall feature a 3 digit LCD screen (0-999 events) for clear event tracking and operate on a battery powered system. | 1.00 | Each |
| 5 | Supply, installation, and testing of an Early Streamer Emission (ESE) Air Terminal, designed and tested in accordance with NFC 17-102 standards, with Delta T ( Initiation Advance ) time tested and certified by an ILAC-accredited high-voltage test laboratory. The air terminal shall be constructed from corrosion-resistant materials to ensure durability and long-term performance. It shall be installed at the highest point of the structure and mounted on a mast of minimum 5.5 meters or as determined by the initiation advance time ( T) calculations, ensuring the required protection radius. The protection radius shall be determined as per NFC 17-102, based on the level of risk protection required (Levels I to IV), with proper Earthings integration for effective lightning dissipation. ES-60 Triggering Advance Time ( T) -60 s, Protection Radius (meters) as per Highest Risk 79 Mtr. | 1.00 | Each |