NTID 42639664
ProcXpert
Share Your purchase requirement, Our ProcXpert team will Connect you to right Supplier.
Inquiry NowCorrigendum Replacement Of U in Srinagar - Complete Tender Details
Find eligibility criteria, important deadlines, bidding requirements, and download official documents for "Corrigendum Replacement Of U" in Srinagar, India.
Public Works Department
Srinagar, Jammu and Kashmir, India
NTID 42639664
- Opening Date : Fri 21st November, 2025
- Closing Date : Thu 20th November, 2025
- ₹ 2385900.00
- NTID 42639664
Tender Description
Documents
Get Complete Tender Details Now - Download the Document!
Download Now – Only ₹200-
Document-1
721.3 kBOil_India_ExtraDoc...Oil_India_ExtraDocument-GCO0449P23.pdf
-
Document-2
721.3 kBOil_India_ExtraDoc...Oil_India_ExtraDocument-GCO0449P23.pdf
Costs
-
EMD
48000.00 -
Document Cost
1000.00 -
Estimated Cost
2385900.00
Latest Corrigendum List
| # | Corrigendum Title | Corrigendum Type |
|---|---|---|
| 1 | Extension in Date | Date |
BOQ Items Total Items : 7 | Total Qty : 49
| # | Item | Quantity | Units |
|---|---|---|---|
| 1 | Supplying, installation, Testing & Commissioning of 120kVA capacity at full load (Unity Power Factor) Monolithic UPS at operating temperature 0 to 40 deg C, Relative humidity 0 to 95%, Online double conversion true sine wave Uninterrupted (UPS) system with N+3 configuration (N denotes total number of UPS which can be paralleled ). The UPS shall include a Rectifier, inverter, battery bank suitable for 30 minutes back up (Battery VAH capacity shall not be less than 1600 VAH per KVA of UPS rating per Hour backup time) on full load (Battery shall be VRLA, SMF in ABS Container) and Static Bypass switch along with provision for manual bypass, suitable isolation transformer (internal/external) for additional protection against neutral faults etc. UPS shall have inbuilt/external phase sequence correction. The UPS systems offered are to be of the latest technology with Digital Control Microprocessor based for reliable operation using Insulated Gate Bipolar Transistor (IGBT)'s both for the rectifier & inverter (3 Level) with PWM (Pulse Width Modulation). Contd... | ||
| 2 | The quality of design, manufacturing and inspection process should confirm to the relevant international standards such as IEC/EN/VDE. The operating efficiency of the UPS systems shall be >95% while operating on battery mode and delivering quality power to the 100% non-linear loads. Current total harmonic effect(ITHD) on the input grid shall be < 5% at 50 %load. (The required LC ( inductor (L) and a capacitor (C)) filters shall be included in UPS cost), extreme power factor kit to be included to limit the input power factor (PF) to 0.99 and output power factor shall be unity (i.e. kw rating of the UPS shall be kva rating x 1 ), however UPS shall be suitable to take load at 0.7 lagging to 0.7 leading power factor loads. UPS shall be suitable for incoming supply AC : 3Phase 400V +/-20%, 50 Hz +/-5 Hz, AC Output voltage: 3Phase 415 Volt, 50 Hz +/- 0.2Hz, Overload capacity of 120% for 10 mins, Sine wave output. Noncondensing, noise level less than 60db at 1 meter distance, protections: Input Under voltage over voltage, abnormal out voltage, battery over charging, output over current, short circuit protection, battery deep discharge protection, 10KV surge. UPS must comply with low voltage electromagnetic compatibility (EMC) achieved as per EN 6204, EN6204 Part I and Part 2, it shall be a Voltage and Frequency Independent (VFI)-type UPS. Communication RS232/RS485/SNMP port open protocol for BMS integration, all hardware & software for iOT Communication as per approved by Engineering in charge. Required battery racks and interconnecting copper conductor cables of suitable size and connectors and all required accessories are inclusive of the cost). Contd... | ||
| 3 | This system must provide a means for logging and alarming of all monitored points plus email notification. Forced air-cooling with integral inbuilt fans with redundancy (if one fan fail UPS should be able to handle at least 80% of the load, Noise Level 65 DB at 1 meter distance. The system shall be in compliance IEC 62040- 1,2 & 3, IS: 16242. Display Panel (minimum) (In-built 7 inch or more LC Display / LED) to display : a) Input: Voltage, current, Frequency. b) Bypass: Voltage, Frequency. c) Output: Voltage, frequency, Current. d) Battery: Voltage, Capacity. e) Load: KVA, KW, Percentage. f)Temperature: STS, Inverter, PFC. g) Event Logging & Statistical Data (On LCD/LED): UPS should capture and display up to 3000 events like: Over temperature / DC Bus Fail / Fan Fail / Fuse Fail / Overload / Short-circuit / Device Fail / Inverter Fail / Rectifier Fail / Bypass Fail, etc. h) Statistical Data: No. of power failures / Transfers to Bypass / Total Running time, etc. i) Mains Mode of Operation /Battery Mode of Operation / Bypass feeding the load / UPS Fault /Battery charging and discharging, overload, battery voltage and battery capacity. j) Audible Alarms : Mains Failure, Battery Low Alarm, UPS Overload, Fault, Shutdown, Input Over, Under Voltage, Output Over, Under Voltage, Battery Over, Under Voltage, Overload and short circuit, Over Temperature. The UPS complete with Batteries, Isolation Transformer, Phase Sequence Corrector and all accessories shall be offered with 3 years comprehensive on-site warranty. | 1 | Job |
| 4 | Fabrication, supply, installation, testing & commissioning of UPS Panel of cubical construction, to be fixed with the existing wall / partition of the UPS room or as per site requirement, fabricated out of 2mm thick sheet steel, compartmentalized with hinged lockable doors, dust and vermin proof, powder coated, cable alley, inter-connection with suitable size solid Aluminium strip, having switchgears and accessories, mountings and internal wiring, earth terminals and earthing, numbering etc. complete in all respects with following Incoming and Outgoings, suitable for operation on 415V, 3 phase, 50Hz, AC Supply with enclosure protection class IP42 as required alongwith Digital Voltmeters / Ammeters / CT Coils of requisite Ratio / Selector Switches / LED Indications / locking arrangement etc. as per the instructions of the Site Engineer: Incoming: (i) 250A, 30-40kA, 4Pole, Thermally adjustable, MCCB : 2 Nos. (ii) 250A, 4P, Onload Manual, Front-operated, Changeover Switch: 1 Nos. (iii) 300A, TPN, Aluminium Busbar: 1 Set. Outgoing: (i) 250A, 30-40kA, 4Pole, Thermally adjustable, MCCB : 2 Nos. (ii) 63A, 10kA, TPN MCB : 2 Nos (iii) 63A, 10kA, DP MCB : 3 Nos | 1 | Nos |
| 5 | Supply, testing, laying, connecting & commissioning of 120 sq. mm, 3.5 Core, Aluminium Conductor, XLPE Sheathed Armoured Cable (ISI Marked), including PVC tagging after every 10 metres. | 10 | Metres |