- Home
- >
- Tender
- >
- Himachal Pradesh Tender
- >
- Department of Military Engineer Services
- >
NTID 43166149
ProcXpert
Share Your purchase requirement, Our ProcXpert team will Connect you to right Supplier.
Inquiry NowCorrigendum Repair maint Of in Kullu - Complete Tender Details
Find eligibility criteria, important deadlines, bidding requirements, and download official documents for "Corrigendum Repair maint Of " in Kullu, India.
Military Engineer Services
Kullu, Himachal Pradesh, India
NTID 43166149
- Opening Date : Fri 16th January, 2026
- Closing Date : Fri 9th January, 2026
- ₹ 900000.00
- NTID 43166149
Tender Description
Documents
Get Complete Tender Details Now - Download the Document!
Download Now – Only ₹200-
Document-1
721.3 kBOil_India_ExtraDoc...Oil_India_ExtraDocument-GCO0449P23.pdf
-
Document-2
721.3 kBOil_India_ExtraDoc...Oil_India_ExtraDocument-GCO0449P23.pdf
Latest Corrigendum List
| # | Corrigendum Title | Corrigendum Type |
|---|---|---|
| 1 | Bid Auto Extn Corrigendum | Bid Auto Extn Corrigendum |
BOQ Items Total Items : 18 | Total Qty : 682.19
| # | Item | Quantity | Units |
|---|---|---|---|
| 1 | M&L in Repair for Earthing complete with galvanized steel earth plate electrode 60 cm x 60 cm x 6 mm thick buried directly in ground (earth pit not less than 2.25 metres deep below normal ground level) with top edge of plate not less than 1.5 metres below normal ground level, connecting to the Galvanised iron strip 25x4 mm by means of bolts, nuts , check nuts and washers of galvanized iron and steel earth wire protected by provision of GI light grade pipe 40 mm bore including provision of concrete pit made from PCC ( 1:2:4) type B-1 (using 20 mm graded stone aggregate) with 40mm thick cover of RCC 1:2:4 reinforced with XPM (Weight not less than 4 Kg/Sqm) and frame of angle iron 40 x 40 x 6 mm and handle of 6 mm dia MS bar made to shape, GI light grade 20 mm bore pipe for watering perforated at bottom, 1.50 metre long placed on top edge of earth plate, common salt & charcoal filling, with fixing arrangement , funnel, wire mesh and earth work in hard/dense soil , returning filling in and removal of surplus soil to a distance not exceeding 50 metres, all as per electrical plate No 5 of SSR 2009 Part-I and connecting to Transformer / Poles all as specified or indicated including testing, complete all as specified and as directed by Engineer-in-Charge. | 5.00 | Each Set |
| 2 | M&L in Repair for Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing/connecting as required 25x4 mm galvanised iron strip, complete all as specified and directed by Engr-in-charge. | 30.00 | RM |
| 3 | M&L in Repair for Earthing complete with galvanized steel earth plate electrode 60 cm x 60 cm x 6 mm thick buried directly in ground (earth pit not less than 2.25 metres deep below normal ground level) with top edge of plate not less than 1.5 metres below normal ground level, connecting to the Galvanised earth lead wire 4.0 mm dia by means of bolts, nuts , check nuts and washers of galvanized iron and steel earth wire protected by provision of GI light grade pipe 40 mm bore including provision of concrete pit made from PCC ( 1:2:4) type B-1 (using 20 mm graded stone aggregate) with 40mm thick cover of RCC 1:2:4 reinforced with XPM (Weight not less than 4 Kg/Sqm) and frame of angle iron 40 x 40 x 6 mm and handle of 6 mm dia MS bar made to shape, GI light grade 20 mm bore pipe for watering perforated at bottom, 1.50 metre long placed on top edge of earth plate, common salt & charcoal filling, with fixing arrangement , funnel, wire mesh and earth work in hard/dense soil , returning filling in and removal of surplus soil to a distance not exceeding 50 metres, all as per electrical plate No 5 of SSR 2009 Part-I and connecting to Poles all as specified or indicated including testing, complete all as specified and as directed by Engineer-in-Charge. | 5.00 | Each Set |
| 4 | M&L for restringing of LT OH conductor ACSR including binding of conductor making jumper connection etc., complete all as specified and directed by Engr-in-charge and directed. Note:- One conductor will be measured as one length. | 198.00 | RM |
| 5 | M&L for cutting of tree branches touching or leaning over overhead power lines and removing of cut tree branches from the site, complete all as specified and as directed by Engineer-in-Charge. | 200.00 | RM |