Find eligibility criteria, important deadlines, bidding requirements, and download official documents for "Development Of Centre For Peri" in Varanasi, India.
Airports Authority of India
Varanasi, Uttar Pradesh, India
NTID 46519612
- Opening Date : Mon 21st September, 2026
- Closing Date : Sat 19th September, 2026
- ₹ 34155000.00
- NTID 46519612
Tender Description
Documents
Get Complete Tender Details Now - Download the Document!
Download Now – Only ₹200-
Document-1
721.3 kBOil_India_ExtraDoc...Oil_India_ExtraDocument-GCO0449P23.pdf
-
Document-2
721.3 kBOil_India_ExtraDoc...Oil_India_ExtraDocument-GCO0449P23.pdf
Costs
-
EMD
1024650.00 -
Document Cost
1180.00 -
Estimated Cost
34155000.00
BOQ Items Total Items : 178 | Total Qty : 66573.28
| # | Item | Quantity | Units |
|---|---|---|---|
| 1 | Electrical Works | ||
| 2 | SH-A(SITC of Cold storage room) SITC of cold storage facility at Varanasi Airport as per following specifications. Cold Room size: Cold Room size shall be nominal dimension of approx 4.0 mtr length x 8.0 mtr width x 3.0 mtr height. Products to be stored: The cold room shall be suitable for storage of Vegetables,Fruits & Flowers. Desired temperature to be achieved in the cold room: The cold room temperature is to be maintained between +8°C to +16°C while the ambient temperature is 45°C. The pull down time shall be upto 15 hrs. Digital temperature indicator cum controller shall be provided. Insulation: The wall and ceiling panel shall be of 100 mm thick cyclopentane PUF insulated panels with prepainted G.I.finish and the floors shall be of 100 mm thick PUF slab with AGI or as per OEM recommendation. Refrigeration: The refrigeration units shall have adequate capacity to maintain the desired temperature range of +8°C to +16°C as required for frequency of door opening per day approx 10 with pemissible refrigerant as per OEM. The condensing unit shall be of outdoor air cooled with required copper piping and to be fixed either in the outer wall of walk in cooler unit or as per site requirement. Power supply suitable for operation of 4wire 3phase 415V, 50Hz: The provision of power supply upto wall mounted power supply cum control panel is not included in this item. The remaining necessary power cord shall be supplied by the successful tenderer upto the cooling units (approx. 5mtrs) Internal Lighting: Required number of lights shall be provided inside the walk in cold room with suitable switch arrangements for ON/OFF. Earthing: The walk in cold room units should be properly earthed with nearest available earth point. ITC: The job includes installation, testing and commissioning of suitable cooling capacity (KW) standalone type walk-in cold storage panels including, level flooring for panel errection, fixing of copper pipes, charging of gas, provision of suitable rating power supply cum control panel, cabling, termination, etc complete as required. | 1 | job |
| 3 | SH-A(SITC of Cold storage room) SITC of cold storage facility at Varanasi Airport as per following specifications. Cold Room size: Cold Room size shall be nominal dimension of approx 6.0 mtr length x 8.0 mtr width x 3.0 mtr height. Products to be stored: The cold room shall be suitable for storage of Vegetables,Fruits & Flowers. Desired temperature to be achieved in the cold room: The cold room temperature is to be maintained between +8°C to +16°C while the ambient temperature is 45°C. The pull down time shall be upto 15 hrs. Digital temperature indicator cum controller shall be provided. Insulation: The wall and ceiling panel shall be of 100 mm thick cyclopentane PUF insulated panels with prepainted G.I.finish and the floors shall be of 100 mm thick PUF slab with AGI or as per OEM recommendation. Refrigeration: The refrigeration units shall have adequate capacity to maintain the desired temperature range of +8°C to +16°C as required for frequency of door opening per day approx 10 with pemissible refrigerant as per OEM. The condensing unit shall be of outdoor air cooled with required copper piping and to be fixed either in the outer wall of walk in cooler unit or as per site requirement. Power supply suitable for operation of 4wire 3phase 415V, 50Hz: The provision of power supply upto wall mounted power supply cum control panel is not included in this item. The remaining necessary power cord shall be supplied by the successful tenderer upto the cooling units (approx. 5mtrs). Internal Lighting: Required number of lights shall be provided inside the walk in cold room with suitable switch arrangements for ON/OFF. Earthing: The walk in cold room units should be properly earthed with nearest available earth point. ITC: The job includes installation, testing and commissioning of suitable cooling capacity (KW) standalone type walk-in cold storage panels including, level flooring for panel errection, fixing of copper pipes, charging of gas, provision of suitable rating power supply cum control panel, cabling, termination, etc complete as required. | 1 | job |
| 4 | SH-A(SITC of Cold storage room) SITC of cold storage facility at Varanasi Airport as per following specifications. Cold Room size: Cold Room size shall be nominal dimension of approx 4.0 mtr length x 8.0 mtr width x 3.0 mtr height. Products to be stored: The cold room shall be suitable for storage of Vegetables,Fruits & Flowers. Desired temperature to be achieved in the cold room: The cold room temperature is to be maintained between -2°C to +8°C while the ambient temperature is 45°C. The pull down time shall be upto 15 hrs. Digital temperature indicator cum controller shall be provided. Insulation: The wall and ceiling panel shall be of 60mm thick cyclopentane PUF insulated panels with prepainted G.I.finish and the floors shall be of 60 mm thick PUF slab with AGI or as per OEM recommendation. Refrigeration: The refrigeration units shall have adequate capacity to maintain the desired temperature range of +2°C to +8°C as required for frequency of door opening per day approx 10 with pemissible refrigerant as per OEM. The condensing unit shall be of outdoor air cooled with required copper piping and to be fixed either in the outer wall of walk in cooler unit or as per site requirement. Power supply suitable for operation of 4wire 3phase 415V, 50Hz: The provision of power supply upto wall mounted power supply cum control panel is not included in this item. The remaining necessary power cord shall be supplied by the successful tenderer upto the cooling units (approx. 5mtrs) Internal Lighting: Required number of lights shall be provided inside the walk in cold room with suitable switch arrangements for ON/OFF. Earthing: The walk in cold room units should be properly earthed with nearest available earth point. ITC: The job includes installation, testing and commissioning of suitable cooling capacity (KW) standalone type walk-in cold storage panels including, level flooring for panel errection, fixing of copper pipes, charging of gas, provision of suitable rating power supply cum control panel, cabling, termination, etc complete as required. | 1 | job |
| 5 | Supply of following 1.1KV grade aluminim conductor XLPE insulated/PVC sheathed armoured cable as per IS 7098 (Part I) 1988 as required. a) 3.5 x 240 sqmm | 1300 | Mtr |