- Home
- >
- Tender
- >
- Kerala Tender
- >
- Department of KITCO Limited
- >
NTID 47125013
ProcXpert
Share Your purchase requirement, Our ProcXpert team will Connect you to right Supplier.
Inquiry NowConstruction Of Critical Care in Kollam - Complete Tender Details
Find eligibility criteria, important deadlines, bidding requirements, and download official documents for "Construction Of Critical Care " in Kollam, India.
- Opening Date : Mon 2nd November, 2026
- Closing Date : Sat 31st October, 2026
- ₹ 14300000.00
- NTID 47125013
Tender Description
Documents
Get Complete Tender Details Now - Download the Document!
Download Now – Only ₹200-
Document-1
721.3 kBOil_India_ExtraDoc...Oil_India_ExtraDocument-GCO0449P23.pdf
-
Document-2
721.3 kBOil_India_ExtraDoc...Oil_India_ExtraDocument-GCO0449P23.pdf
Costs
-
EMD
50000.00 -
Document Cost
5900.00 -
Estimated Cost
14300000.00
BOQ Items Total Items : 56 | Total Qty : 5595
| # | Item | Quantity | Units |
|---|---|---|---|
| 1 | HVAC WORKS | ||
| 2 | OD5251/2026-2027:Supply, Installation ,testing and commissioning of 58 HP minimum capacity Air-cooled VRF (Variable Refrigerant Flow) Outdoor unit with variable speed inverter driven multiple compressors complete with suitable capacity drive motors conforming to IE3 as per IS 12615, air cooled condenser, R410A/R407C refrigerant, oil separator, with all accessories, and safety devices like thermal protector, pressure relief valve, high-low pressure cut off etc . Necessary structural supports, ODU vibration isolators shall be considered . Equipment shall be suitable for 3 phase, 415 V, 50Hz supply along with suitably rated starter panel & associated accessories, suitable interconnecting control cabling between IDUs, ODUs ,power cabling between isolator and single/multiple outdoor units along with associated electrical accessories. Required supports including structural supports /RCC/ cement concrete foundation shall be included as part of equipment . COP at AHRI conditions shall not be less than 3.1 and IEER not less than 6.5. The efficiency of the equipment shall meet ECBC/ASHRAE latest standards etc. complete in all respects as per the technical specifications.(single feeder power source will be provided for outdoor units). | 1 | no |
| 3 | OD5250/2026-2027:Supply, Installation ,testing and commissioning of 34 HP minimum capacity Air-cooled VRF (Variable Refrigerant Flow) Outdoor unit with variable speed inverter driven multiple compressors complete with suitable capacity drive motors conforming to IE3 as per IS 12615, air cooled condenser, R410A/R407C refrigerant, oil separator, with all accessories, and safety devices like thermal protector, pressure relief valve, high-low pressure cut off etc . Necessary structural supports, ODU vibration isolators shall be considered . Equipment shall be suitable for 3 phase, 415 V, 50Hz supply along with suitably rated starter panel & associated accessories, suitable interconnecting control cabling between IDUs, ODUs ,power cabling between isolator and single/multiple outdoor units along with associated electrical accessories. Required supports including structural supports /RCC/ cement concrete foundation shall be included as part of equipment . COP at AHRI conditions shall not be less than 3.1 and IEER not less than 6.5. The efficiency of the equipment shall meet ECBC/ASHRAE latest standards etc. complete in all respects as per the technical specifications.(single feeder power source will be provided for outdoor units). | 1 | no |
| 4 | OD5249/2026-2027:Supply, installation, testing and commissioning (SITC) of VRF-compatible Air Handling Unit (AHU) of specified capacity, complete with AHU kit suitable for integration with VRF system, factory/field-mounted Variable Frequency Drive (VFD) of suitable rating, starter panel, associated controls, thermostat, temperature sensors and electrical controller for UV system, complete with all standard fittings, including double-skin construction casing with pre-painted GI/aluminium panels and PUF insulation, thermal break profile, structural base frame, access doors, vibration isolation arrangement and flexible duct connectors; belt drive/plug centrifugal fan statically and dynamically balanced, driven by TEFC, squirrel cage, 3-phase induction motor of suitable capacity and IE3 efficiency conforming to IS 12615, with suitable drive package and cushy-foot mounting; cooling coil of copper tube and aluminium fin construction compatible with refrigerant R410A/R407C, complete with headers, distributors, filter drier and first charge of refrigerant gas;multi-stage air filtration system comprising Filter Bed-1 of ISO Coarse 60% efficiency pre-filters and Filter Bed-2 of ISO ePM2.5 80% efficiency fine filters conforming to ISO 16890, complete with filter housings, holding frames, proper sealing arrangements, access doors and all necessary accessories for maintenance and replacement; UVGI system comprising UV emitters with reflectors mounted on coil surface using removable extruded aluminium frames with minimum intensity of 12 W per sq.ft. of coil surface area, ensuring uniform distribution of UV intensity across the coil surface, including safety interlocks and control system; stainless steel (SS) drain pan with proper slope connected to PVC drain piping (up to 5 m) insulated with 9 mm thick nitrile rubber insulation, finished with 7 mil woven fibreglass cloth and fungicidal protective coating, including U-trap, necessary elbows, fittings and accessories; outlet volume control dampers, complete power and control wiring, control cabling, cabling from power supply point, earthing, interconnections, and all necessary accessories, supports, fasteners, and consumables; including complete installation, alignment, testing, balancing, and commissioning to achieve specified performance parameters, all in accordance with approved technical specifications and relevant standards such as ASHRAE/NBCS/ISO, complete in all respects. 25TR (10000 CFM) - 50 mm of WG ESP | 1 | no |
| 5 | OD5248/2026-2027:Supply, installation, testing and commissioning (SITC) of VRF-compatible Air Handling Unit (AHU) of specified capacity, complete with AHU kit suitable for integration with VRF system, factory/field-mounted Variable Frequency Drive (VFD) of suitable rating, starter panel, associated controls, thermostat, temperature sensors and electrical controller for UV system, complete with all standard fittings, including double-skin construction casing with pre-painted GI/aluminium panels and PUF insulation, thermal break profile, structural base frame, access doors, vibration isolation arrangement and flexible duct connectors; belt drive/plug centrifugal fan statically and dynamically balanced, driven by TEFC, squirrel cage, 3-phase induction motor of suitable capacity and IE3 efficiency conforming to IS 12615, with suitable drive package and cushy-foot mounting; cooling coil of copper tube and aluminium fin construction compatible with refrigerant R410A/R407C, complete with headers, distributors, filter drier and first charge of refrigerant gas;multi-stage air filtration system comprising Filter Bed-1 of ISO Coarse 60% efficiency pre-filters and Filter Bed-2 of ISO ePM2.5 80% efficiency fine filters conforming to ISO 16890, complete with filter housings, holding frames, proper sealing arrangements, access doors and all necessary accessories for maintenance and replacement; UVGI system comprising UV emitters with reflectors mounted on coil surface using removable extruded aluminium frames with minimum intensity of 12 W per sq.ft. of coil surface area, ensuring uniform distribution of UV intensity across the coil surface, including safety interlocks and control system; stainless steel (SS) drain pan with proper slope connected to PVC drain piping (up to 5 m) insulated with 9 mm thick nitrile rubber insulation, finished with 7 mil woven fibreglass cloth and fungicidal protective coating, including U-trap, necessary elbows, fittings and accessories; outlet volume control dampers, complete power and control wiring, control cabling, cabling from power supply point, earthing, interconnections, and all necessary accessories, supports, fasteners, and consumables; including complete installation, alignment, testing, balancing, and commissioning to achieve specified performance parameters, all in accordance with approved technical specifications and relevant standards such as ASHRAE/NBCS/ISO, complete in all respects. 20TR (8000 CFM) - 50 mm of WG ESP | 2 | no |